UPS MTD-XL
Technical Data
72
12. Technical Data
12.1 Specifications of the device
Model MTD-XL
1000
1500
2000
3000
Capacity
Watt
900 W
1350 W
1800 W
2700 W
Input
Input voltage range
161 - 276 VAC
Input frequency
range
50/60 Hz ± 5 Hz for normal operating mode
40 - 70 Hz for generator mode
Output
Output voltage
220 / 230 / 240 VAC
Voltage changes
(battery mode)
± 5 %
Frequency
50 Hz or 60 Hz
Voltage type
sine wave
Overload
Normal operating
mode
110 % - 0 %, + 8 %: shut down appliances after 3
minutes
150 % - 0 %, + 10 %: shut down appliances after
200 ms
Battery mode
110 % ± 6 %; shut down appliances after 30 sec-
onds
120 % ± 6 %; shut down appliances after 100 ms
Battery
Battery type
independent of battery banks
Charging current
4.5 A
4.5 A
4 A
4 A
Charging time
independent of battery banks
External battery
mode (EBM)
Battery
12 V / 9 AH
Interface
RS232
standard
Dry contact
optional
USB
standard
SNMP
optional
EPO
standard