UPS MTD-XL
UPS Device Description
33
3.2.4 Mains Input
IEC connector socket 10 A for MTD-XL 1000 and 1500.
IEC connector socket 16 A for MTD-XL 2000 and 3000.
Mains power supply connection with enclosed supply cable with two-pin
earthed plug.
The protective earth conductor must be connected!
Please always note the specified input voltage on the identification tag or
in the technical specifications in this operating manual respectively.
3.2.5 EPO-port
The remote shut-down port is used for turning off appliances. This function can
be used, to turn of appliances via an external potential-free contact.
This circuit has to be separated from high-voltage circuits by reinforced
insulation.
The remote shut-down input may not be connected to circuits that are directly
connected with the mains power supply.
Feeders must have reinforced insulation
The load capacity of the remote shut-down switch must be at least 24 V DC /
20 mA and it must be designed as a special snap-switch without any connec-
tion to any other circuit.