SIPART DR22Serial SIPART 6DR2210 Bus InterfaceOperating Instructions C79000-B7476-C155-03Explanation to the manual C79000-G7476-C154ContentsPage1 Hard
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0310D 1-byte structure switch which can only be read from the computerConte
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0311Contents: Addresses of the structure switch from the menu ”StrS”HiAd: 4
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03122.3.5 Parameter ”onPA”Contents: Addresses of the online parameters from
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0313HiAd: 59HLoAd: 00H to 1DHNAMELoAd BYTE TYPE RANGE DIM NOTESP11P12P13P14
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03142.3.6 Parameter ”OFPA”Contents: Addresses of the online parameters from
for S1 = 4and 6 only %Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03152)The display format for A1 to A4 is a function o
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0316Contents: Addresses of the offline parameters from the menu “oFP A” at
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03172.3.7 Parameter ”PASt”Contents: Addresses of the offline parameters fro
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03182.3.8 Parameter ”CAE4”/”CAE5”D Parameters which can be read/written fro
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03192.3.9 Function definitions ”FdEF”Address of blocks which can not be act
SIPARTR, SITRANSR, SIMATICRare Siemens registered trademarks. All other products or system names are (registered) trademarks of theirrespective owners
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03202.3.10 Function connection ”FCon”The content of the interconnectable in
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0321Identifications of outputs which can be entered into the FCon sinks (Hi
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03222.3.11 Position functions ”FPoS”Time processing of the defined function
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0323NAMELoAd BYTE TYPE NOTESAE1AAE2AAE3AAE4AAE5ABCHBEHC0HC2HC4H22222LIN””””
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0324D Data which can be read/writte from the computerHiAd: 45HLoAd: E0H to
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0325Writing into/readingHiAd: 45HLoAd: E3H, 1 ByteByte ST4 MeaningBit SES C
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0326Writing into/readingHiAd: 45H HiAd: 45HLoAd: E7H LoAd: E8HByte ST61)Byt
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0327only readableHiAd: 45HLoAd: D7H, 1 ByteByte ST3 MeaningBitError-/status
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0328only readableHiAd: 45HLoAd: D1H, 1 ByteByte ST9 MeaningBitActual, effec
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0329only readableHiAd: 45H HiAd: 45HLoAd: D3H, 1 Byte LoAd: D5HByte STN1 Me
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0331 Hardware: SIPART 6DR2210Refer to the Instructions C79000-G7476-C154 fo
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0330only readableHiAd: 45HLoAd: DAHByte ST12 MeaningBit7 Error option (2/3/
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03312.3.14 Representation of parameters and process variablesCompared to th
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03322.3.15 Copy protection by means of a keywordFrom the software version C
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03333 PROFIBUS3.1 PROFIBUS ModuleThe PROFIBUS module 6DR2803--8P can also b
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0334Each process variable is defined (addressed) by 2 parameter bytes.Param
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03353.4 Description of the Communication ObjectsEach communication object h
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03363.4.3 Interpretation of Variable Index(byte 1/subindex 5)According to a
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03373.5 Universal Communication ObjectsThe following objects (PNU < 100)
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03387.) The system identifier consisting of 4*4 byte ASCII is writable/read
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03393.) Reading DR2210 PNU 520 [0x208] (if not via cyclical process data)(d
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-034D Character conventionsSTX02HStNo40H to 5FH Station number , 32 possible
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03406.) Writing ”onpa” parameter VV1 = 2500 PNU 101 [0x65] and c7 = 10.00 P
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03416.4.) W riting ST_U Bit.1 = 0Master --> Slave (command) Slave -->
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03427.3.) W riting 2. ParameterMaster --> Slave (command) Slave --> M
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03439.) Writing DR2210 process variables YH_2 PNU 527 [0x20F] via AKZ and P
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-034411.) Writing cyclical of DR2210 of 4 process values in the following se
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03453.8 Table of the DP communication ob jectsParameter ”onPA”| Description
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0346| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0347| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0348| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0349| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0352.3.2 Safety features, error handlingError monitoring of the controller
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0350Parameter ”PASt”| Description element (subindex)| |variabl/|PNU |Identi
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0351Parameter ”CAE4/CAE5”| Description element (subindex)| |variabl/|PNU |I
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0352| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0353| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0354| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0355| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0356| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0357| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0358| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0359| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-036D Sequence of functions:ReceiveThe controller receives the characters in
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0360| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0361| Description element (subindex)| |variabl/|PNU |Identification/|Array|
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0362Processdata (read-/writeable)| Description element (subindex)| |variabl
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03632.) PNU 332: binary inputs ”BExx”| BIT 15: BE8 | BIT 7: x| BIT 14: BE7
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-03646.) PNU 373: Status ”STes” (writeable)| BIT 15: 0 | BIT 7: CB| BIT 14:
E Siemens AG 1999 All rights reservedOrder No. C79000-B7476-C155AG 0400 66 GBSiemens AGBereich Automatisierungs- und AntriebstechnikGeschäftsgebiet A&
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0376. The DR22 stores each message for the destination into the RAM. The pa
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0384. If the structuring messages are transmitted without ”Start structurin
Operation InstructionsSerial SIPART 6DR2210 Bus InterfaceC79000-B7476-C155-0392.3.4 Structure switch ”StrS”Note: adjustable range is from 0 to “Max”Co